01/02 AWB8230-1413GB
Mains contactors
165
Mains contactors Mains choke
h
The mains contactors listed here assume the network’s
rated current (I
LN
) without mains choke or mains filter.
Their selection is based on the thermal current (AC-1).
Caution!
Jog mode must not be used through the mains contactor
(rest period f 180 s between switching off and on)
DF6-340- DF6 phase
current
Mains contactor
Open/enclosed Model
I
LN
[A] I
th
AC-1 [A]
11K 24 35/30 DIL0M
15K 32
18K5 41
55/44 DIL1M
22K 47
30K 63
90/80 DIL2M
37K 77
45K 94
100/– DIL3M80
55K 116
160/– DIL4M115
75K 149
90K 176
225/– DILM185
110K 215
132K 253
250/– DILM225
Figure 155: DE4-LN... mains chokes
h
When the frequency inverter works at its rated current
limit, the frequency inverter’s greatest possible output
voltage (U
2
) is , due to the mains choke, reduced to about
96 % of the mains voltage (U
LN
).
DF6-340- Mains current (I
LN
)
of the DF6 without
mains choke
Assigned
mains choke
11K 24 DE4-LN3-15K
15K
32 DE4-LN3-15K
18K5
41 DE4-LN3-22K
22K
47 DE4-LN3-30K
30K
63 DE4-LN3-45K
37K
77 DE4-LN3-45K
45K
94 DE4-LN3-55K
55K
116 DE4-LN3-75K
75K
149 DE4-LN3-90K
90K
176 DDK2,5-9,2
110K
215 DDK3,2-9,2
132K
253 DDK4,0-9,2
h
For technical data of the DE4-LN mains chokes, see the
installation instructions AWA8240-1711, for those of the
DDK series, see the main Industrial Switchgear catalog.
h
Mains chokes reduce the magnitude of the current
harmonics up to about 30 % and increase the lifespan of
frequency inverters and upstream-connected switching
devices.