Operating the DF6
01/02 AWB8230-1413GB
50
Connection examples
Operation using an external potentiometer
Configuration of the parameters
Method of operation
You can start the frequency inverter in a clockwise direction with
terminal FW and in an anticlockwise direction with terminal 5. If
both terminals are closed simultaneously, a stop signal is issued.
With the externally connected potentiometer, the required
frequency setpoint (voltage setpoint) can be defined.
You can use the measuring instrument to display the frequency
(PNU C027 = 00) or, for example, the motor current
(PNU C027 = 01). With PNU b081, you can adjust analog output
FM to the corresponding measurement range of the measurement
device (frequency or current can be displayed).
Operation through an analog setpoint value
Configuration of the parameters
Method of operation
Inputs FW and 5 function exactly as described in the previous
example.
With digital input 3 (configured as AT), you can change over from
a voltage setpoint value (0 to 10 V) to a current setpoint value
(4 to 20 mA).
Instead of the wiring on terminal 3, which is fixed or realized using
a switch, you can set PNU C013 to 01. Digital input 3 is then
configured as a break contact (NC).
The circuit example also includes a motor PTC thermistor. It is
important to use a screened control cable and to lay the motor PTC
thermistor cable separately from the other motor cables. However,
the screen should be earthed at the inverter side only.
Figure 43: Connecting an external potentiometer
PNU Value
Function
A001 01 Setpoint definition through control signal
terminal strip
A002 01
Start signal through FW(D)/REV terminals
F002 10
Acceleration time in s
F003 10
Deceleration time in s
––
FWD: Start clockwise operation on
digital input FW
C005 01
REV: Start anticlockwise operation on
digital input 5
C027 00
Indication of the output frequency (analog)
through the measurement device connected to
terminals L and FM
b081 80
Adjustment of the analog frequency display
connected to terminals L and FM
REV
FWD
24 V
0
P24FW5FMLLOH
R
(1 – 10 k
O
)
+
0 – 10 V
1 mA
PES PES
PES
Figure 44: Analog setpoint definition
PNU Value
Function
A001 01 Setpoint definition through control signal terminal
strip
A002 01
Start signal through FW(D)/REV terminals
F002 10
Acceleration time in s
F003 10
Deceleration time in s
––
FWD: Start clockwise operation on
digital input FW
C005 01
REV: Start anticlockwise operation on
digital input 5
C003 16
AT: Changeover to current setpoint value
(4 to 20 mA)
AT
REV
FWD
24 V
0
P24FW35THCM1LOI
4 – 20 mA
E
PESPES
efesotomasyon.com - Klockner Moeller - inverter