01/02 AWB8230-1413GB
Other functions
147
Initialization
Two different types of initialization are available:
• Clearing the fault history register
• Restoring the default parameter settings (default setting)
To delete the fault history register or to restore the factory default
settings, proceed as follows:
X Make sure that PNU b085 holds the value 01.
X Under PNU b084 (initialization), enter 00, 01 or 02.
X Press the ENTER key to save the value.
X On the keypad, press both arrow keys and the PRG key at the
same time and keep them pressed.
X While holding the arrow and PRG keys, briefly press the OFF
key.
X Now release all keys again. The display shows d001.
Initialization is now complete.
Country version
Here, you define the country-specific parameter set which will be
loaded during initialization (a PNU b084).
Frequency factor for display through PNU d007
The product of the output frequency and this factor is displayed
under PNU d007.
OFF key disabled
Here, you can disable the OFF key located on the keypad or remote
operating unit.
PNU Name Adjustable in RUN mode Value Function WE
Normal Extended
b084 Initialization – – 00 Clearing the fault history register 00
01 Restoring the default parameter settings
02 Deleting the fault history register and restoring the default
settings
PNU Name Adjustable in RUN mode Value Function WE
Normal Extended
b085 Country
version
– – 00 Japan 01
01 Europe
02 USA
PNU Name Adjustable in RUN mode Value Function WE
Normal Extended
b086 Frequency
factor
j j 0.1 to 99.9 The product of the value displayed under PNU d001 and this
factor is displayed at PNU d007. This value is also available
at the FM terminal.
1.0
PNU Name Adjustable in RUN mode Value Function WE
Normal Extended
b087 OFF key
disabled
– j 00 OFF key always active 00
01 OFF key not active with control through the FWD/REV
terminals