01/02 AWB8230-1413GB
Other functions
143
Display mode
With this function, you can specify the parameters which the DF6
displays. Only these displayed parameters can then be changed:
• All parameters: PNU b037 = 00 (default)
• Parameters which are relevant to the programmed parameters:
PNU b037 = 01
• Only the parameters saved under PNU U001 to U012,
PNU b0037 = 02 (a section “User-defined parameters –
parameter group U”, page 150).
All parameters: PNU b037 = 00 (default)
By default, the DF6 displays all parameters and all parameters can
be changed.
Relevant parameters: PNU b037 = 01
With this setting, the DF6 displays only those parameters which
are connected with ones that are already programmed. If, for
example you set a constant V/f characteristic under PNU A044
(default value: 00), the parameters for an adjustable V/f
characteristic are not shown (PNU b100 to b113). The table below
shows, which parameters are hidden when this option is set.
PNU Value PNUs which are hidden when PNU b037 is
set to 01
Function
A001 01 A005, A006, A011 to A016, A101 to A105, A111
to A114, C081 to C083, C121 to C123
Analog inputs O, OI, O2
A002 01, 03, 04, 05
b087 OFF key disabled
A019 00
A028 to A035 Fixed frequencies
C001 to C005 02, 03, 04, 05
A044, A244 02
b100 to b113 Voltage and frequency characteristic
A051 01
A052 to A059 DC braking
A071 01
A072 to A076, C044 PID control
A094 01
A095 to A096 Second time ramp
A294 01
A295 to A296
b013, b213, b313 02
b015 to b020 Electronic motor protection
b021 01, 02
b022, b023 Overcurrent limit
b024 01, 02
b025, b026 Overcurrent limit 2
b095 01, 02
b090, b096 BRD function
C001 to C005 06
A038, A039 Jog mode
08
F202, F203, A203, A204, A220, A241 to A244,
A261, A262, A292 to A296, b212, b213, H203 to
H206
Second parameter set
11
b088 Motor shutdown and free run stop (coasting)
18
C102 Reset
27, 28, 29
C101 Acceleration/deceleration motor potentiometer
A044 00, 01
A041 to A043 Voltage boost function
A244 00, 01
A241 to A243 Voltage boost function
A044 03, 04, 05
b040 to b046, H001, H002 0 Hz limitation
A244 03, 04
b040 to b046, H202
A097 01, 02, 03
A131 Curvature of acceleration ramp
A098 01, 02, 03
A132 Curvature of acceleration ramp
b098 01, 02
b099, C085 Thermistor function
b050 01
b051 to b054 Behaviour on power failure
b120 01
b121 to b126 Brake control