Setting Parameters
01/02 AWB8230-1413GB
108
Start signal
With PNU A002, you specify how the start signal is to be issued:
• through digital inputs, for example the FW input or a digital
input configured as REV,
• with the ON key on the keypad,
• through the RS 485 serial interface,
• through slot 1 or 2 for optional modules.
Base frequency
The base frequency is the frequency at which the output voltage
has its maximum value.
End frequency
If a constant-voltage frequency range exists beyond the transition
frequency set with PNU A003 , define this range with PNU A004 .
The maximum end frequency must not be smaller than the base
frequency.
PNU Name Adjustable in RUN mode Value Function WE
Normal Extended
A002 Start signal – – 01 The motor start signal is issued through digital inputs, for
example through the FW input or a digital input configured
as REV.
01
02 The signal for starting the motor is issued by the ON key on
the keypad.
03 The motor start signal is issued through the RS 485
interface.
04 The motor start signal is issued through the optional module
in slot 2.
05 The motor start signal is issued through the optional module
in slot 2.
PNU Name Adjustable in
RUN mode
Value WE
Nor-
mal
Exten-
ded
A003
A203
Base
frequency
– – 30 to 400 Hz 50
Figure 104: End frequency
f
1
: Base frequency
f
2
: End frequency
PNU Name
Adjustable in
RUN mode
Value WE
Nor-
mal
Exten-
ded
A004
A204
End
frequency
– – 30 to 400 Hz 50
0
f
1
f
2
100
[%]
U
f
[Hz]