Programmable digital inputs
1to5
65
Programmable digital inputs 1 to 5
Various functions can be assigned to terminals 1 to 5. Depending
on your requirements, you can configure these terminals as
follows:
• anticlockwise start signal (REV),
• selection inputs for various fixed frequencies (FF1 to FF4),
• reset input (RST),
•etc.
The terminal functions for programmable digital inputs 1 to 5 are
configured with PNU C001 to C005, i.e. with PNU C001, you
specify the function of digital input 1, with PNU C002 the function
of digital input 2, etc. Note, however, that you cannot assign the
same function to two inputs at the same time.
Programmable digital inputs 1 to 5 are configured by default as
make contacts. If, therefore, you want to activate the function of
an input terminal, you must close the corresponding input (i.e.
connect the input terminal to terminal P24). Conversely, to
deactivate the input terminal, the input must be opened.
Table 11: Digital inputs 1 to 5
For a detailed description of the input functions, see the pages
listed in table 12.
Table 12: Functions of the digital inputs
Caution!
If an EEPROM error occurs, (fault message E08), all
parameters must be checked to ensure that they are
correct (especially the RST input).
PNU Terminal Adjustable in
RUN mode
Value WE
Normal Exten-
ded
C001 1 – j a table 12 18
C002 2
16
C003 3
03
C004 4
02
C005 5
01
Value Function Description a page
01 REV Start/stop anticlockwise 67
02 FF1
First fixed frequency input 68
03 FF2
Second fixed frequency input
04 FF3
Third fixed frequency input
05 FF4
Fourth fixed frequency input
06 JOG
Jog mode 78
07 DB
DC brake 85
08 SET
Selection of the second
parameter set
84
09 2CH
Second acceleration and
deceleration time
73
11 FRS
Motor shutdown and free run
stop (coasting)
74
12 EXT
External fault 75
13 USP
Unattended start protection 76
14 CS
Heavy starting duty 88
15 SFT
Parameter protection 81
16 AT
Setpoint definition through
current signal
72
18 RST
Reset 77
20 STA
Pulse start (3-wire) 91
21 STP
Pulse stop (3-wire) 91
22 F/R
Direction of rotation (3-wire) 91
23 PID
Activation of PID control 92
24 PIDC
Reset integral component 92
27 UP
Acceleration
(motor potentiometer)
82
28 DWN
Deceleration
(motor potentiometer)
82
29 UDC
Reset frequency
(motor potentiometer)
82
32 SF1
Bitwise fixed frequency
selection
70
33 SF2
34 SF3
35 SF4
36 SF5
37 SF6
38 SF7
39 OLR
Current limit switch over 87
no NO
No function –
efesotomasyon.com - Klockner Moeller - inverter