Programming the Control
Signal Terminals
01/02 AWB8230-1413GB
66
You can optionally configure the digital inputs as break (NC)
contacts. To do this, enter 01 under PNU C011 to C015
(corresponding to digital inputs 1 to 5).
An exception applies to the RST input (reset), which can only be
operated as a make (NO) contact. FW is configured as a make (NO)
contact under PNU C019.
Table 13: Configuring digital inputs as break contacts
Caution!
If you configure digital FW or REV inputs as break contacts
(the default setting is as a make contact), the motor starts
immediately. They should not be reconfigured as break
contacts unless this is unavoidable.
PNU Terminal Value Adjustable in RUN mode Function WE
Normal Extended
C011 1 00 or 01 – j 00: Make
contact
01: Break
contact
00
C012 2
C013 3
C014 4
C015 5
C019 FW