External fault message (EXT)
When the digital input configured as EXT is activated, fault
message E12 is issued (for example to be used as input for
thermistor contacts). The fault message remains active even if the
EXT input is deactivated again and must be acknowledged with a
reset.
A reset can be carried out with:
the RST input or
the OFF key.
Alternatively, the supply voltage can be switched off and on
again.
X Program one of the digital inputs 1 to 5 as EXT by entering the
value 12 under the corresponding PNU (C001 to C005).
Figure 63: Digital input FW configured as FWD (start/stop clockwise
operation) and digital input 3 as EXT (external fault
message)
Figure 64: Function chart for EXT (external fault message)
n
M
: Motor speed
K14: Signalling relay contact K14
(if the signalling relay has been set to 13 (THM) under PNU C026
a Motor coasts to a stop
EXT
FWD
P24FW3
FWD/REV
EXT
n
M
RST
K14
a
Warning!
After a reset, the motor restarts immediately if a start
signal (FWD or REV) is active.
efesotomasyon.com - Klockner Moeller - inverter