Time ramps
129
Time ramps
During operation, you can change over from the time ramps set
under PNU F002 and F003 to those programmed under PNU A092
and A093. This can be done either by applying an external signal
to input 2CH at any time or when the frequencies configured under
PNU A095 and A096 are reached.
Figure 127: Time ramps
t
1
: Acceleration time 1
t
2
: Acceleration time 2
PNU A095
2CH/PNU A095
t
1
t
2
f
t
PNU Name Adjustable in RUN mode Value Function WE
Normal Extended
A092
A292
Second
acceleration
time
j j 0.01 to 3600 s Setting times for the second acceleration and deceleration
time
0.1 to 999.9 s: Resolution 0.1 s
1000 to 3000 s: Resolution 1 s
15
A093
A293
Second
deceleration
time
A094
A294
Changeover
from the first to
the second
time ramp
00 Changeover to the second time ramp if an active signal is
present on a 2CH digital input.
00
01 Changeover to the second time ramp when the frequencies
entered in PNU A095 and/or A096 are reached
A095
A295
Acceleration
time
changeover
frequency
0.00 to
400.0 Hz
Here, set a frequency at which the changeover from the first
to the second acceleration time is to take place.
0.0
A096
A296
Deceleration
time
changeover
frequency
0.00 to
400.0 Hz
Here, set a frequency at which the changeover from the first
to the second deceleration time is to take place.
0.0