01/02 AWB8230-1413GB
Analog inputs
terminals O, O2 and OI
61
Matching of terminals O, O2 and OI
With PNU C081 to C083 and PNU C121 to C123, you can adapt
the analog setpoint signals at terminals O, O2 and OI to your
requirements:
Matching of terminal O 0 to +10 V
Matching of setpoint signal: PNU C081
Zero point matching: PNU C121
Terminal O2, –10 V to +10 V
Matching of setpoint signal: PNU C083
Zero point matching: PNU C123
Terminal OI: 4 to 20 mA
Matching of setpoint signal: PNU C082
Zero point matching: PNU C122
Caution!
These parameters are not reset to their default values
during initialization.
PNU Name Adjustable in RUN mode Value Function WE
Normal Extended
C081 Matching of
terminal O
j j 0 to 65530 Here, you can match the setpoint signal (0 to +10 V)
supplied at analog input O with reference to the output
frequency.
Depen-
ding on
DF6
C082 Matching of
terminal OI
Here, you can match the setpoint signal (4 to 20 mA)
supplied at analog input OI with reference to the output
frequency.
C083 Matching of
terminal O2
Here, you can match the setpoint signal supplied at analog
input O2 (–10 V to +10 V) with reference to the output
frequency.
C121 Zero-point
matching,
terminal O
0 to 6553
(65530)
Here, you can match the setpoint signal (0 to +10 V)
supplied at analog input O with reference to the zero point.
C122 Zero-point
matching,
terminal OI
Here, you can match the setpoint signal (4 to 20 mA)
supplied at analog input OI with reference to the zero
point.
C123 Zero-point
matching,
terminal O2
Here, you can match the setpoint signal (–10 V to +10 V)
supplied at analog input O2 with reference to the zero
point.