01/02 AWB8230-1413GB
Analog outputs – AM, AMI and
FM
57
Analog outputs – AM, AMI and FM
The analog outputs provide various physical variables, which you
can select and some of which you can adjust to meet your specific
needs. Terminals AM, AMI and FM are connected to chassis
through terminal L.
Voltage output (AM)
The AM terminal provides the variables listed in the table below in
the form of a 0 to 10 V voltage signal.
X In PNU C028, specify the variable which the AM terminal is to
provide.
X In PNU B080, specify the gain factor and in PNU C086 the
offset.
You cannot change all parameters in RUN mode. Editable
parameters in RUN mode are marked with a “j” in the “normal”
column of the table below. With PNU b031, you can set additional
parameters which are editable in RUN mode (a section
“Software protection (SFT)”, page 81). These additional
parameters are marked “j” in the “Extended” column.
Adjustable in RUN mode
Normal Extended
j
PNU Function Adjustable in RUN mode Value Function WE
Normal Extended
b080 Gain, AM
terminal
j j 0 to 255 Gain of the voltage output 180
C028 Output, AM
terminal
j 00 Output frequency: 0 Hz to end frequency PNU A004
(a section “End frequency”, page 108)
00
01 Output current: 0 to 200 %
04 Output voltage: 0 to 100 %
05 Inverter input power: 0 to 200 %
06 Thermal load ratio: 0 to 100 %
07 Ramp frequency: 0 Hz to end frequency PNU A004
(a section “End frequency”, page 108)
C086 Offset, AM
terminal
j j 0 to 10 V Voltage increase 0.0