Programming the Control
Signal Terminals
01/02 AWB8230-1413GB
78
Jog mode (JOG )
When the digital input configured as JOG is activated, the motor
can be operated in jog mode. This mode is used, for example, for
manual setting up of a machine by issuing a start signal on the FW
or REV input with a relatively low frequency without applying an
acceleration ramp to the motor.
X First, under PNU A038, enter
the frequency which is to be applied to the motor when jog
mode is active.
Make sure that the frequency is not too high, as it is applied
directly to the motor without an acceleration ramp. This could
cause a fault message. Set a frequency below 5 Hz.
X Because the start signal is issued through the FWD or REV input
in jog mode, PNU A002 must be set to 01.
X Under PNU A039, you determine how the motor is to be braked.
X Program one of the digital inputs 1 to 5 as JOG by entering the
value 06 under the corresponding PNU (C001 to C005).
Figure 69: Digital input FW configured as FWD (start/stop clockwise
operation) and digital input 3 as JOG (jog operation)
Figure 70: Function chart for JOG (jog mode)
n
M
:Motor speed
a Depending on the setting of PNU A039
00: Coasting
01: Deceleration ramp
02: DC braking
JOG
FWD
P24FW3
a
JOG
FWD/REV
n
M
a
Caution!
Make sure that the motor has stopped before using
jog mode.
efesotomasyon.com - Klockner Moeller - inverter