01/02 AWB8230-1413GB
Start/stop
79
PNU Name Adjustable in RUN mode Value Function WE
Normal Extended
A002 Start signal 01 The signal for starting the motor is issued through the digital
inputs configured as FW or REV.
01
02 The signal for starting the motor is issued by the ON key on
the keypad.
A038 Frequency in
jog mode
j j 0 to 9.99 Hz The frequency to be applied to the motor in jog mode. 1.0
A039 Type of motor
stop in jog
mode
j 00 Stop signal active: the motor coasts to halt 00
01 Stop signal active: the motor is decelerated to standstill
under a deceleration ramp
02 Stop signal active: the motor is decelerated to standstill
under DC braking
03 Jog mode without prior motor stop: the motor coasts to halt
04 Jog mode without prior motor stop: the motor is decelerated
to standstill under a deceleration ramp
05 Jog mode without prior motor stop: the motor is decelerated
to standstill under DC braking
h
Operation in jog mode is not possible when the jogging
frequency set under PNU A038 is less than the start
frequency set under PNU b082 (a section “Run signal
(RUN)”, page 96).
h
Jog mode can only be activated when the frequency
inverter is in the Stop state if the values 00 to 02 have
been set under PNU C039.