Appendix
01/02 AWB8230-1413GB
166
RFI filter
RFI filters have discharge currents to earth, which, in the event of
a fault (phase failure, load unbalance), can be higher than the
rated values. To avoid dangerous voltages, the filters must be
earthed before use.
For discharge currents f 3.5 mA, VDE 0160 and EN 60335 specify
that
• the protective conductor must have a cross-section f 10 mm
2
or
• a second protective conductor must be connected, or
• the continuity of the protective conductor must be monitored.
The table below lists radio interference filters with their matching
frequency inverters.
Figure 156: RFI filter
h
Radio interference filters DE6-LZ3-013-V4 to
DE6-LZ3-064-V4 can be mounted below (footprint
mounting) or – from DE6-LZ3-080-V4 – to the side of the
frequency inverter (book-type mounting).
DF6-340-... RFI filter Rated voltage U
e
Maximum leakage
current in rated
operation
Maximum leakage
current under fault
conditions
Power loss of RFI filter at
rated operation
V mA mA W
11K DE6-LZ3-032-V4 3 ~ 480 + 10 % < 30 280 14
15K
18K5
DE6-LZ3-064-V4 550 36
22K
30K
37K
DE6-LZ3-080-V4 690 32
45K
DE6-LZ3-115-V4 750 38
55K
75K
DE6-LZ3-150-V4 380 40
90K
DE6-LZ3-220-V4 380 60
110K
132K
DE6-LZ3-013-V4 600 50