01/02 AWB8230-1413GB
Connection examples
51
Operation with fixed frequencies
Configuration of the parameters
Method of operation
Inputs FW and 5 function exactly as described in the first example.
With the activation of one or both fixed frequency inputs FF1 and
FF2, the current frequency setpoint applied to the motor is
replaced by the fixed frequency determined by FF1 and FF2, and
the motor brakes or accelerates according to the fixed frequency
applied. If neither of the fixed frequency inputs FF1 and FF2 is
activated, the frequency setpoint is determined through analog
inputs O (voltage setpoint value) or OI (current setpoint value). The
wiring for these terminals is not shown in this circuit example. For
the combination of the individual fixed frequency values,
a section “Fixed frequency selection (FF1 to FF4)”, page 68.
The circuit example also contains the parameter settings for one
output signal each at terminals K23-K24 and K33-K34. The output
signal type is configured with PNU C021 for relay output K23-K24
and with PNU C022 for relay output K33-K34.
Figure 45: Fixed frequency definition
PNU Value
Function
A001 01 Setpoint definition through control signal
terminal strip
A002 01
Start signal via FWD/REV terminals
F002 10
Acceleration time in s
F003 10
Deceleration time in s
––
FWD: Start clockwise operation on
digital input FW
C002 01
AT: Changeover to current setpoint value
(4 to 20 mA)
C003 16
FF1: Fixed frequency input 1
C004 02
FF2: Fixed frequency input 2
C005 03
REV: Start anticlockwise operation on digital
input 5
C021 00
RUN output signal at terminal K23-K24
C022 01
FA1 output signal at terminal K33-K34
A021 f
1
The fixed frequency to be applied when FF1 is
active and FF2 is inactive is entered here.
A022 f
2
The fixed frequency applied when FF1 is inactive
and FF2 is active is entered here.
A023 f
3
The fixed frequency is applied when FF1 and FF2
are both active is entered here.
REV
FF2
FF1
AT
FWD
24 V H
P24FW2345
PES
FA1
5...30 V H, F 250 V h
K33 K34
RUN
K23 K24
efesotomasyon.com - Klockner Moeller - inverter