01/02 AWB8230-1413GB
Warnings
155
Warnings
Conflicting parameter inputs (for example minimum operating
frequency PNU A062 > end frequency PNU A004). In addition, the
PRG LED flashes until the parameters are corrected.
The following warnings may be issued:
Display Meaning
H001
H
201
Maximum operating frequency, PNU A061 (A261) > End frequency, PNU A004 (A204, A304)
H
002
H
202
Minimum operating frequency, PNU A062 (A262) >
H
004
H
204
Nominal motor frequency, PNU A003 (A203, A303) >
H
005
H
205
Setpoint frequency, PNU F001 or
PNU A020 (A220, A320)
>
H
006
H
206
Fixed frequencies 1 to 15, PNU A021 to A035 >
H
012
H
212
Minimum operating frequency, PNU A062 (A262) > Maximum operating frequency, PNU A061 (A261)
H
015
H
215
Setpoint frequency, PNU F001 or
PNU A020 (A220, A320)
>
H
016
H
216
Fixed frequencies 1 to 15, PNU A021 to A035 >
H
021
H
221
Maximum operating frequency, PNU A061 (A261) < Minimum operating frequency, PNU A062 (A262)
H
025
H
225
Setpoint frequency, PNU F001,
PNU A020 (A220, A320)
<
H
031
H
231
Maximum operating frequency, PNU A061 (A261) < Increased starting frequency, PNU b082
H
032
H
232
Minimum operating frequency, PNU A062 (A262) <
H
035
H
235
Setpoint frequency, PNU F001 or
PNU A020 (A220, A320)
<
H
036 Fixed frequencies 1 to 15, PNU A021 to A035 <
H
037 Jogging frequency, PNU A038 <
H
085
H
285
Setpoint frequency, PNU F001 or
PNU A020 (A220, A320)
= Frequency jump 1 to 3 g jump width, PNU A063 to
A068
1)
H086 Fixed frequencies 1 to 15, PNU A021 to A035 =
efesotomasyon.com - Klockner Moeller - inverter