Programming the Control
Signal Terminals
01/02 AWB8230-1413GB
60
Analog inputs terminals O, O2 and OI
You can specify the setpoint frequency through three analog
inputs:
Terminal O: 0 to 10 V
Terminal O2: –10 V to +10 V
Terminal OI: 4 to 20 mA
The reference potential for the analog inputs is terminal L.
Frequency setpoint definition
By default, the frequency setpoint definition is made through the
voltage input (0 to 10 V). Alternatively, you can enter the setpoint
value through one of the other analog inputs or a combination of
two analog inputs. To do this, configure a digital input with the AT
function (a section “Analog input changeover (AT)”, page 72).
The two inputs are specified under PNU A005 and A006.
The table below shows how you can link analog inputs O, O2 and
OI with PNU A005 and A006.
PNU Name Adjustable in RUN mode Value Function WE
Normal Extended
A005 AT selection 00 Changing over from O to OI 00
01 Changing over from O to O2
A006 O2 selection
00 O2 signal only 00
01 Sum of signals at O2 and O or OI without direction reversal
02 Sum of signals at O2 and O or OI with direction reversal
Main frequency
setpoint value
input
O2 signal sum Reversal of
direction with
O2
AT input
configured
A006 A005 Input AT
OYes YesYes 02 00 Off
01
No
Yes 01 00 Off
01
No No
Yes 00 00 Off
00 01
Add O + OI Yes Yes
No 00
02
No
01
O2 No Yes
Yes 02 01 On
00
No
01
OI Yes Yes
Yes 02 00 On
Yes No
01
No No
00