Appendix
01/02 AWB8230-1413GB
160
with external braking resistor 55 % 50 % –
with external braking device and external
braking resistor
– – 40 to
200 %
35 to
200 %
110 to
170 %
90 to
150 %
70 to
120 %
60 to
100 %
45 to
70 %
40 to
60 %
30 to
50 %
25 to
40 %
With DC injection braking
Braking occurs at frequencies below the minimum frequency (minimum frequency, braking time and braking torque are user-definable)
Inputs
Frequency setting Keypad Setting through keys or potentiometer
External
signals
•0 to 10VH, input impedance 10 kO;
• –10 V to +10 V H, input impedance 10 kO;
• 4 to 20 mA, load impedance 250 O
• Potentiometer f 1kO, recommended 4.7 kO
Clockwise/anticlockwise
operation (start/stop)
Keypad
ON key (for Start) and OFF key (for Stop); default setting = clockwise operation
External
signals
• Digital input FW for clockwise operation (FWD)
• Digital input programmable as REV for anticlockwise operation
Digital control inputs programmable as
• REV: Start/stop anticlockwise
• FF1 to FF4: Fixed frequency selection
• JOG: Jog mode
• DB: DC braking active
• SET: Second parameter set active
• 2CH: Second time ramp
• FRS: Free run stop (coasting)
• EXT: External fault message
• USP: Unattended start protection
• CS: Heavy starting duty
• SFT: Software protection
• AT: Select analog input
• RST: Reset
• STA: Pulse start (3-wire)
• STP: Pulse stop (3-wire)
• F/R: Direction of rotation (3-wire)
• PID: PID control active
• PIDC: Reset integral component of PID control
• UP: Remote access, acceleration
• DWN: Remote access, deceleration
• UDC: Reset frequency with remote control
• OPE: Setpoint value through operator panel
• SF1 to SF7: Bitwise frequency selection
• OLR: Current limit changeover
• NO: No function
DF6-340-...
11K 15K 18K5 22K 30K 37K 45K 55K 75K 90K 110K 132K