EasyManua.ls Logo

Moeller DF6-340 Series - Page 174

Moeller DF6-340 Series
184 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
01/02 AWB8230-1413GB
Standard form for user defined
parameter settings
171
PNU Function Units WE Page Setpoint
b001 Restart mode
00: Fault message
01: 0 Hz start
02: Synchronization to current motor speed and
acceleration
03: Synchronization and deceleration
–00 133
b002 Permissible power failure duration [s] 1.0 133
b003 Waiting time before restart [s] 1.0 133
b004 Fault message issued immediately
00: No fault on intermittent mains failure
01: Fault on intermittent mains failure
02: No fault on intermittent mains failure at
standstill and deceleration
–00 133
b005 Number of restart attempts
00: 16 restart attempts
01: Unlimited number of restart attempts
–00 134
b006 Mains phase failure detection
00: Inactive
01: Active
–00 134
b007 Synchronization frequency on return of mains power [Hz] 0.00 134
b012 Tripping current for electronic motor protection device [A] I
e
(inverter) 136
b212 Tripping current for electronic motor protection device
(second parameter set)
[A] I
e
(inverter) 136
b013 Characteristic for electronic motor protection device
00: Enhanced protection
01: Normal protection
03: User-definable protection
–01 136
b213 Characteristic for electronic motor protection device
(second parameter set)
00: Enhanced protection
01: Normal protection
03: User-definable protection
–01 136
b015 Frequency 1 for user-definable motor protection
characteristic
[Hz] 0 137
b016 Tripping current 1 for user-definable motor protection
characteristic
[A] 0.0 137
b017 Frequency 2 for user-definable motor protection
characteristic
[Hz] 0 137
b018 Tripping current 2 for user-definable motor protection
characteristic
[A] 0.0 137
b019 Frequency 3 for user-definable motor protection
characteristic
[Hz] 0 137
b020 Tripping current 3 for user-definable motor protection
characteristic
[A] 0.0 137
b021 Motor current limitation 1
00: Inactive
01: Active in every operating status
02: Inactive during acceleration, otherwise active
–01 138
b022 Tripping current 1 for motor current limitation [A] I
e
x 1.5 138
b023 Time constant 1 of motor current limitation [s] 1.00 138
efesotomasyon.com - Klockner Moeller - inverter

Table of Contents

Other manuals for Moeller DF6-340 Series

Related product manuals