01/02 AWB8230-1413GB
Start/stop
71
.
PNU Name Adjustable in RUN mode Value Function WE
Normal Extended
A001 Defined
frequency
setpoint
00 Definition with the potentiometer on the keypad 01
01 Definition through analog input O (0 to 10 V), OI
(4 to 20 mA) or O2 (–10 V to +10 V H)
02 Definition via PNU F001 and/or PNU A020
03 Definition through RS 485 serial interface, terminals: RP,
2 x SN and SP
04 Definition via optional card at slot 1
05 Definition via optional card at slot 2
A019 Selection of
fixed frequency
actuation
00 Binary (FF1 to FF4) 00
01 Bitwise (SF1 to SF7)
A020
A220
Frequency
setpoint value
j j 0 to PNU A004 You can enter a frequency setpoint value. You must set
PNU A001 to 02 for this purpose.
0.0
A021 Fixed
frequency
You can assign a frequency to each of the seven fixed
frequency parameters of PNU A021 to A027.
A022
A023
...
A027
F001 Input/display
frequency
value
Indication of the current frequency setpoint value or the
current fixed frequency.
To save modified values, press the ENTER key according to
the selection of the digital inputs configured as SF1 to SF7.
Resolution g0.1 Hz