EasyManua.ls Logo

Moeller DF6-340 Series - Page 89

Moeller DF6-340 Series
184 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Programming the Control
Signal Terminals
01/02 AWB8230-1413GB
86
X Program one of the digital inputs 1 to 5 as DB by entering the
value 07 under the corresponding PNU (C001 to C005).
X In PNU A053, enter a delay time t (a fig. 77) from 0 to 5.0 s,
which is to expire before DC braking takes effect after activation
of the DB input.
X Under PNU A054, set a braking force between 0 % and 100 %.
Figure 77: Function chart for DB (DC braking)
f
o
: Output frequency
a Start signal through keypad
FWD/REV
DB
f
O
DB
f
O
a
DB
f
O
a
t
efesotomasyon.com - Klockner Moeller - inverter

Table of Contents

Other manuals for Moeller DF6-340 Series

Related product manuals