01/02 AWB8230-1413GB
Programmable relay outputs
K11 to K34
95
X If you configure a programmable relay output as FA2, you must
also, under PNU C042, enter the frequency from which the FA2
signal is active during acceleration.
X With PNU C0043, set the respective frequency which is to
remain active until the FA2 signal is deactivated during
deceleration.
X Do the same for FA3.
X Program one of the relay outputs K23-K24 or K33-K34 as FA1
to FA3 output by entering one of the following values in the
corresponding PNU (C021 or C022) or in PNU C026 for
signalling relay contacts K11-K12:
–FA1: 01
–FA2: 02
–FA3: 06
By default, FA1 is assigned to relay output K23-K24.
Figure 88: Relay output K23-K24 configured as FA1/FA2/FA3
(frequency reached/exceeded)
Figure 89: Function chart for FA2 (frequency exceeded)
fo:Output frequency
f
1
: 1 % of the end frequency (PNU A004, A204)
f
2:
2 % of the end frequency (PNU A004, A204)
FA1/
FA2/
FA3
5...30 V
0
.
250 V
D
K23 K24
FA2
PNU C042
PNU C043
B
O
B
1
B
2
Figure 90: Function chart for FA3 (frequency reached)
f
o
: Output frequency
f
1
: 1 % of the end frequency (PNU A004, A204)
f
2
: 2 % of the end frequency (PNU A004, A204)
FA3
f
O
PNU C042
PNU C043
f
1
f
1
f
2
f
2
PNU Name Adjustable in RUN mode Value Function WE
Normal Extended
C042 Frequency
switching
threshold
during
acceleration
j 0 to 400 Hz The relay output configured as FA2 or FA3 (K11-K12,
K23-K24, K33-K34) is activated when the frequency entered
here is exceeded.
0.0
C043 Frequency
switching
threshold
during
deceleration
The relay output configured as FA2 or FA3 (K11-K12,
K23-K24, K33-K34) remains active, as long as the frequency
entered here is exceeded during deceleration (a fig. 89
and fig. 90).