HarshIO 600 eIP
26
IP67 IO-Link Modules for EtherNet/IP
Networks LEDs
The left side bi-color red/green LED is network status indicator (NET) and the right side bi-color red/green LED
is internal module status indicator (MOD).
LED
Color State
Meaning
NET
OFF
No UB power supply or no IP address assigned
Blinking Red
IP address assigned & connection time-out
Rotary position changed while IO exchange running
Fixed Red
IP Conflict detected (Duplicate IP)
Fixed Green
IP address assigned & connection established (no communication problem)
Blinking Green
IP address assigned & no connection established
Blinking Green/Red
Self-test on power up
MOD
OFF
No UB power supply
Blinking Red
Major Recoverable Fault
- IP Conflict detected
- Rotary position changed while IO exchange running
- Configuration Control changed (Set attr3 object 0xF5)
- Interface Configuration changed (Set attr5 object 0xF5)
- IP lost (Ex : DHCP mode)
Fixed Red
Major Unrecoverable Fault
Fixed Green
Module is started and operational
Blinking Green
Module is started but no configuration has been received through an IO connection yet.
Blinking Green/Red
Self-test on power up
NET indicator
MOD indicator