IP67 IO-Link Modules for EtherNet/IP
Use of the rotaries
3 decimal rotary switches are located under the window and oriented as shown below. “x100 x10 x1” labels
are printed below of the rotary (PCB silkscreen).
Note!
The module window shall be screwed with a torque of 0.3 Nm to ensure a correct
sealing to achieve IP67 rating and shall be closed during working operation.
The user shall check regularly that the torque of module window is respecting the
screwing value 0.3 Nm
The rotary switch position is only read at the boot of the HarshIO module. Any modification of the position will
require a power cycle (ON OFF ON) or a reset of the module
The HarshIO module is out-of-box configured with rotary position 000. This configuration corresponds to stored
IP address mode 500 with DHCP mode activated. When connecting to a network with a DHCP server, an IP
address is automatically assigned to the module.
Assigning an IP address using 0xF5 TCP/IP Object allows defining permanently this IP address for the
following module startup. No rotary switches modification would be required.
To change or set the IP address, the operator has the possibility to use one of the following methods:
Overwrite the 4
th
byte of the IP address stored in non-volatile
memory.
IP Address: 192.168.1.xyz (xyz from 1 to 254)
IP mask: 255.255.255.0
Gateway: 192.168.1.1
Note!
If the IP address is 192.168.1.1 then
the gateway will be 0.0.0.0
Note!
When using static IP address mode,
the IP address is stored in the Flash
memory of the module.