EasyManuals Logo

Murr Elektronik MVK-MP User Manual

Murr Elektronik MVK-MP
74 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #59 background imageLoading...
Page #59 background image
Manual MVK-MP
V 3.5 59
6.1.3.2. DO8(DO8) Art.-No. 55290
Bus data
Transfer protocol ................................................ Profibus-DP acc. to DIN 19245
Transfer rates ..................................................... 9,6/19,2/45,45/93,75/187,5/500/
............................................................................ 1500/3000/6000/12000 kBaud
Baud rate detection ............................................ automatically
Operating modes ................................................ Sync- and freeze mode are supported
Addressing ......................................................... 1 … 99 via BCD rotary switch
ID number ........................................................... 0x064A hex
Supply
Operating voltage U
B
.......................................... 24 V
Supply voltage range ......................................... 18 ... 30 V
Current consumption (without inputs) ................ 150 mA
Reverse polarity protection
Module electronics .............................................. Yes
Actuators ............................................................. No
Outputs
Max. no. of outputs .............................................. 16
Nominal current ................................................... 1.6 A
Max. total current ................................................ 9 A
Over voltage protection ....................................... Yes (suppressor diode)
Cable length ........................................................ 0.75 mm²10 m
............................................................................ 0.34 mm² 5 m
Cable diameter .................................................... 1.5 mm²
Signal delay ......................................................... 2 5 ms
Max. switching frequency at resistive load .......... 20 Hz
Max. lamp load .................................................... 10 W

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Murr Elektronik MVK-MP and is the answer not in the manual?

Murr Elektronik MVK-MP Specifications

General IconGeneral
BrandMurr Elektronik
ModelMVK-MP
CategoryControl Unit
LanguageEnglish

Related product manuals