6.1.3.6. DI8(DI8) Art.-No. 55307
Bus data
Transfer protocol ................................................ Profibus-DP acc. to DIN 19245
Transfer rates ..................................................... 9,6/19,2/45,45/93,75/187,5/500/
............................................................................ 1500/3000/6000/12000 kBaud
Baud rate detection ............................................ automatically
Operating modes ................................................ Sync- and freeze mode are supported
Addressing ......................................................... 1 … 99 via BCD rotary switch
ID number ........................................................... 0x064A hex
Supply
Operating voltage U
B
.......................................... 24 V
Supply voltage range ......................................... 18 ... 30 V
Current consumption (without inputs) ................ 150 mA
Sensor supply .................................................... 200 mA per sensor
Short-circuit protection for sensors .................... Multifuse,
............................................................................ up to 100 mA load automatic start
............................................................................ from 100 mA load reset required
Tripping time multifuse ....................................... 1s at I
K
1 A and 23°C
Reverse polarity protection inputs ...................... yes
Inputs / diagnostics
Max. no. of inputs ................................................ 16
Delay time with signal change ........................... 2 … 5 ms
Input characteristic ............................................. EN 61131-2, type 2
Input filter............................................................. approx. 1 ms
Over voltage protection ....................................... Yes (suppressor diode)
Reverse polarity protection
Module electronics .............................................. Yes
Sensors ............................................................... No
Actuators ............................................................. No

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Murr Elektronik MVK-MP and is the answer not in the manual?

Murr Elektronik MVK-MP Specifications

General IconGeneral
BrandMurr Elektronik
ModelMVK-MP
CategoryControl Unit
LanguageEnglish

Related product manuals