Control
43
FIGHTER 1140
Hot water temperature
Menu 1.1 Periodtime HW/Total
The time of the hot water period and the time for the
whole period are shown here. Shown for both hot
water charging and heat when necessary:
Time HW-charge/Max when hot water charging is in
progress. Time heating/Max when heating is in
progress.
Menu 1.3 MAX-time HW-period
Here you select how much time of the period time
(menu 1.1) is to be used to heat the hot water when
there is a need of both heating and hot water. The
value is adjustable between 5 and 60 minutes.
Menu 1.4 HW-temp/Starttemp.HW
The temperature when the heat pump starts to work
with the hot water heater is set here. When brackets
with a minus are shown, this means the high pressure
pressostat has tripped during hot water charging and
FIGHTER 1140 has automatically lowered the set
temperature with the value in brackets. The reduction
is removed when the value is changed. The value is
adjustable between 25 and 55 °C.
Menu 1.5 HW-temp/Stoptemp.HW
The temperature when the heat pump/immersion
heater should stop heating the water is set here.
When brackets with a minus are shown, this means
the high pressure pressostat has tripped during hot
water charging and FIGHTER 1140 has automatically
lowered the set temperature with the value in brackets.
The reduction is removed when the value is changed.
The value is adjustable between 30 and 60 °C.
Menu 1.8 Interval XHW
How often the hot water temperature is increased from
the normal level to the “Extra hot water” level is shown
here. The time is adjustable between 0 and 90 days.
Extra hot water is shut-off when 0 is set. Extra hot
water starts when the value has been confirmed.
Menu 1.9 Next XHW action
Future increases to the “Extra hot water” level are
shown here.
Menu 1.10 HW running time
How long hot water heating has been in progress is
shown here (accumulated).
20 (60)min
Periodtime HW/Total
1.1
14days
Interval XHW
1.8
90h 10 min
HW running time
1.10
20 min
MAX-time HW-period
1.3
50.0 (47)°C
HW-temp/Starttemp.HW
1.4
50.0 (54)°C
HW-temp/Stoptemp.HW
1.5
Menu 1.6 Stop Temp. XHW
The desired stop temperature for extra hot water is set
here. The value is adjustable between 40 and 70 °C.
50.0 (60)°C
Stop Temp. XHW
1.6
10-26 10:31
Next XHW action
1.9
N
N
N
N
Menu 1.2 Time period
The length of time is set here. The value is adjustable
between 5 and 60 minutes.
60min
Time period
1.2
N
U
U
Menu 1.7 Stop compressor XHW
The temperature to stop the compressor for extra hot
water is set here. The value is adjustable between 50
and 60 °C.
50.0 (55)°C
Stop compressor XHW
1.7
U
U
U
Menu 1.11 Return
Pressing the enter button returns you to menu 1.0
Return
1.11