Menu 9.2.12 Oper. mode brinepump
The operating mode for the brine pump is set here.
Selectable options are:
Intermittent: The brine pump starts 20 seconds
before and stops 20 seconds after the compressor.
Continuous: Continuous operation.
10 days. cont: Continuous operation for 10 days.
Then the pump shifts to intermittent mode.
Service menus
55
FIGHTER 1140
Operating settings
Menu 9.2.11 Brine pressostat
You set here whether an external brine
pressostat/load monitor is connected to the load moni-
tor card.
Off
Brine pressostat
9.2.11
S
Menu 9.2.13.0 Docking
Settings regarding external docking can be made in
the sub-menus to this menu. NOTE! These settings
must be confirmed by switching the heat pump off
and on within 30 minutes.
Docking
9.2.13.0
S
Menu 9.2.13.1 Docking type
This menu is used to select the docking option:
Select 1 for docking to an electric boiler.
Select 2 for docking to a gas boiler.
Select 3 for docking to an oil boiler.
Select 4 for fixed condensing
The value is adjustable between -1 and 5.
1
Docking type
9.2.13.1
S
Menu 9.2.13.2 Immersion heat type
Binary 3 step: Preselected
Linear 3 step: Selected with an external electric boiler.
Binary 7 step: Selected with an external electric boiler.
Off: Selected to disengage electrical addition.
Off
Immersion heat type
9.2.13.2
S
Menu 9.2.13.3 Hot water
This menu is used to select whether there is a hot
water heater or not. When “On” is selected Menu 1.0
and its sub-menus become visible.
The value is adjustable “On” or “Off”.
Off
Hot water
9.2.13.3
S
Menu 9.2.13.4 Boiler Temp/act mixv
This menu shows the boiler temperature and here you
select at which temperature the oil shunt starts to work
(open).
40 (55)°C
Boiler temp/act mixv
9.2.13.4
S
Intermittent
Oper. mode brinepump
9.2.12
S
Menu 9.2.13.5 Start value OilPower
In this menu you can set the number of degree min-
utes when the oil addition should start to work. Applies
to docking option 3.
The value is adjustable between -30 and -500
-400
Start value OilPower
9.2.13.5
S
Menu 9.2.13.6 Oil burner on
In this menu you set the running time for the oil burn-
er.
The value can be set between 0 and 12 hours.
12 h
Oil burner on
9.2.13.6
S
Menu 9.2.13.7 Return
Pressing the enter button returns you to menu 9.2.13
Return
9.2.13.7
Menu 9.2.14 Factory setting
Return to the factory settings in FIGHTER 1140, “Yes”
or “No”. When returning to the factory settings the lan-
guage switches to English.
No
Factory setting
9.2.14
S