EasyManua.ls Logo

Notifier UDACT

Notifier UDACT
132 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
General
UDACT Instruction Manual PN 50050:H 09/16/2002 103
Appendix G: NFS-640
General
The UDACT is capable of reporting a maximum of 99 zones or 700 points when used with the
NFS-640.
Mounting
If the UDACT is not mounted within the cabinet that contains the NFS-640, then it must be mounted
remotely in an ABS-8R/RB or UBS-1 enclosure placed within 6000 feet (1828.8 meters) of the control
panel. For mounting instructions see "Remote Installation" on page 22.
If the NFS-640 is contained in a CAB-4 Series cabinet, then the UDACT may be mounted to a
CHS-M2, CHS-4, or CHS-4MB chassis within that cabinet. For mounting instructions see "Internal
Installation" on page 20.
Wiring
CAUTION: Remove all power from the control panel by disconnecting AC and batteries before
making any connections to prevent personal and/or circuit damage.
Connections
Refer to Figure 25 and Figure 26 on page 104.
Connect the communication line between the EIA-485 terminal block TB13 on the CPU-640 and TB1
terminals 3 and 4 on the UDACT, being certain to observe polarity.
If no other devices are connected to the EIA-485, install a 120 ohm EOL resistor across UDACT TB1
terminals 3 and 4.
Connect the
Ground Wire (PN 71073, provided) from the UDACT EARTH terminal on TB3 to the CHS-4
Chassis or to a solid building earth ground.
Connect 24VDC filtered, non-resettable power from the CPU-640 TB7 to TB1 terminals 1 and 2 on the
UDACT.
Notes:
1. Ferrite cores, PN 29090, are recommended for all applications.
2. Recommended wire is 12 AWG (3.25mm
2
) to 18 AWG (0.75mm
2
), twisted pair, shielded cable.
Connect only one end of shield: a) shield may be connected to cabinet (earth ground) at fire alarm
panel, or b) shield may be connected to TB1 Terminal 5 (Shield) at UDACT as shown in Figure 25.
Note: The shield end that is not connected should be insulated to prevent accidental grounding. Do not connect both
ends of shield under any circumstance since a ground fault may result.
1. Conduit is recommended for external wire runs. Consult local building codes.
2. Refer to "Specifications" on page 13 for power requirements.
!
Technical Manuals Online! - http://www.tech-man.com

Table of Contents