UDACT Instruction Manual PN 50050:H 09/16/2002 43
Programming Reference Sheets
Options
To enter Programming, press MODE, then 7764, then ENTER/STORE.
00 01 02 03 04 05 06 07 08 09 10 11 12 13
14 15 Primary Phone Number: Enter 'F' to represent the end of the number.
16 Primary Communication Format: Enter 0 - F.
1718 19 20 Primary Account Code: Valid keys are 0-F.
21 22 23 24 Primary 24-Hour Test Time: Enter military time (i.e. 1400 for 2 PM).
25 Primary Number Test Time Interval: Enter '0' for 24-hour; '1' - 12-hour.
26 27 28 29 30 31 32 33 34 35 36 37 38 39
40 41 Secondary Phone Number: Enter 'F' to represent the end of the number.
42 Secondary Communication Format: Enter 0-F.
43 44 45 46 Secondary Account Code: Valid keys are 0-F.
47 48 49 50 Secondary 24-Hour Test Time: Enter military time (1400 for 2 PM).
51 Secondary Number Test Time Interval: Enter '0' for 24-hour; '1' - 12-hour.
52 53 Start Monitoring Address: Valid entries are 01 through 32.
54 55 End Monitoring Address: Valid entries are 01 through 32.
56 UDACT Communication Selection: Enter '0' to disable UDACT communication; '1' for zone
reporting receive only communication; '2' for zone reporting receive/transmit communication; '3' for
point reporting receive only; or '4' for point reporting receive/transmit.
57 Backup Reporting: Enter '0' to have secondary phone number act as backup only; '1' to have
secondary phone number receive all reports and messages along with primary phone number.
58 Touchtone/Rotary Select: Enter '0' for touchtone dialing; '1' for rotary dialing.