Programming Reference Sheets
44
UDACT Instruction Manual PN 50050:H 09/16/2002
59 Make/Break Ratio: If rotary dialing is selected in Address 58; Enter '0' for a 67/73 make/
break ratio; '1' for a 62/38 make/break ratio.
60 Leave default of 0.
61 Leave default of 0.
62 AC Loss Reporting Delay: Enter '0' for no time delay after AC loss; '1' for 6 hour delay; '2' for
7 hour delay; '3' for 8 hour delay; '4' for 9 hour delay; '5' for 10 hour delay; '6' for 11 hour delay; '7' for
15 hour delay; '8' for 16 hour delay; '9' for 17 hour delay; 'A' for 18 hour delay; 'B' for 19 hour delay; 'C'
for 20 hour delay; 'D' for 21 hour delay; 'E' for 22 hour delay; or 'F' for 23 hour delay.
63 Host Panel ID: Enter '0' for AFP-100; '1' for System 500; '3' for System 5000; '4' for System
5000 with AIM-200; '5' for AFC-600, NFS-640; '7' for AM2020/AFP1010/INA, NCA, and NFS-3030;
'8' for AFP-300/AFP-400; or leave default of '6' for AFP-200; all other entries are invalid.
64 65 Loop Number: Factory set to '00'. Valid entries are 00 through 97
66 67 68 Device/Zone Number for General Reports: Factory set to '000'. Valid entries
are 000 through 999.