EasyManua.ls Logo

Notifier UDACT

Notifier UDACT
132 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Wiring
68
UDACT Instruction Manual PN 50050:H 09/16/2002
Wiring
CAUTION: Remove all power from the control panel by disconnecting AC and batteries before
making any connections to prevent personal and/or circuit damage.
Connections
With internal installation the EIA-485 circuit and 24VDC are provided directly from the J16 connector.
Note: A 120 ohm EOL resistor is not required on the UDACT EIA-485 terminals when it is installed inside the AFP-100
cabinet.
For external connections refer to Figure 16 on page 68.
Connect the communication line between the EIA-485 terminal block TB5 on the AFP-100 and TB-1
terminals 3 and 4 on the UDACT, being certain to observe polarity.
If last device or no other devices are connected to the external EIA-485, install a 120 ohm EOL resistor
(PN 71244) across UDACT TB1 terminals 3 and 4.
Connect the
Ground Wire (PN 71073, provided) from the UDACT EARTH terminal on TB3 to a solid
building earth ground.
Connect 24VDC filtered, non-resettable power from terminal block TB4 on the AFP-100 to TB1
terminals 1 and 2 on the UDACT.
Notes:
1. Ferrite cores, PN 29090, are recommended for all applications.
2. Recommended wire is 12 AWG (3.25mm
2
) to 18 AWG (0.75mm
2
), twisted pair, shielded cable.
Connect only one end of shield: a) shield may be connected to cabinet (earth ground) at fire alarm
panel, or b) shield may be connected to TB1 Terminal 5 (Shield) at UDACT as shown in Figure 16.
Note: The shield end that is not connected should be insulated to prevent accidental grounding. Do not connect both
ends of shield under any circumstance since a ground fault may result.
3. Conduit is recommended for external wire runs. Consult local building codes.
4. Refer to "Specifications" on page 13 for power requirements.
Below is a remote installation of a UDACT with an AFP-100:
Figure 16 UDACT and AFP-100
!
EARTH
Comm FAILURE
+24V
+24V
GND
RS+
RS–
SHIELD
RS+
Rs–
ACS/TERM
TERM
COMMONCOMMON
BATT -
+24V POWER+24V RESET
BATT +
UDACT-19.cdr
Solid Earth
Ground
Connection
To Phone Lines
(supervised)
DO NOT USE
AFP-100 Cabinet
AFP-100 Circuit Board
ABS-8R or UBS-1
Ferrite Core
Technical Manuals Online! - http://www.tech-man.com

Table of Contents