Loop Break Alarm
Display Action Response
Press MENU 1) Press MENU, if necessary, until the "Loop Break" prompt appears.
Press ENTER 2) Display advances to
"Loop Break Enable/Disable" submenu.
LOOP BREAK ENABLE/DISABLE SUBMENU:
Press ENTER 3) Display flashes
"
enbl
" or "
dsbl
".
Press MAX 4) Scroll through the available selections: Enable (
enbl
) or Disable (
dsbl
).
Press ENTER 5) Display flashes
"
strd
" message and advances to "Loop Value" menu.
Loop Break is an additional safety feature intended to monitor the rate of change of the process value, while approaching
the SPI. It is strictly intended as an additional warning system, therefore its use is entirely optional. An active Loop Break
will cause the setpoint digits to blink in a rotating pattern. If the process value reaches the setpoint the blinking will stop
and
Loop brA1
is completed successfully, otherwise
Loop brA1
will flash and will activate
Alr1
.
L.B.AL
ENBL
L00P
BR.AL