CP TD1 Reference Manual V 1.44
86
In Figure 6-16, the test procedure for a two-winding transformer is shown,
according to IEEE 62 1995 [3.4].
Figure 6-16 Two-winding transformer test according to IEEE 62-1995
Test Mode Energize Ground Guard UST Measure
GST HIGH LOW C
H
GST LOW HIGH C
L
Alternative test for C
HL
UST HIGH LOW C
HL
UST LOW HIGH C
HL
LOW HIGH
C
HL
C
L
C
H