ConfigLoadErr
Register name Sys.ConfigLoadErr
Description Read error in saved settings
Range 0 to 1
Details 0: No error
1: System file setting error
Detection timing When power is turned ON or the Controller is reset.
Recovery Cycle the power supply, or issue reset command ($$$)
Effects Operate with default settings.
Cause and cor-
rection
Cause (Assumed cause) Correction Prevention
Settings are incorrect. If the re-initialization com-
mand ($$$***) is executed,
and the error no longer oc-
curs, review the settings.
None
The CPU Unit or the CK3W
Unit has failed
If this error persists even
after you make the above
corrections, replace the
CPU Unit or the CK3W
Unit.
None
Precautions/
Remarks
None
6 Troubleshooting