100
Exchanging Data with the CPU Unit Section 3-5
DM Allocation Contents The following table shows the allocation of DM words and bits for both normal
and adjustment mode.
CJ1W-AD041-V1
Note For the DM word addresses, m = D20000 + (unit number x 100).
CJ1W-AD081-V1
Note For the DM word addresses, m = D20000 + (unit number x 100).
DM word Bits
1514131211109 876543210
D(m) Not used. (Settings are ignored.) Not used. Input use setting
Input
4
Input
3
Input
2
Input
1
D(m+1) Not used. (Settings are ignored.) Input signal range setting
Input 4 Input 3 Input 2 Input 1
D(m+2) Input 1: Mean value processing setting
D(m+3) Input 2: Mean value processing setting
D(m+4) Input 3: Mean value processing setting
D(m+5) Input 4: Mean value processing setting
D(m+6)
to (m+17)
Not used. (Settings are ignored.)
D(m+18)
Conversion time/resolution setting
00: Conversion time of 1 ms and resolution of 4,000
C1: Conversion time of 250 µs and resolution of 8,000
Operation mode setting
00: Normal mode
C1: Adjustment mode
DM word Bits
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
D(m) Not used. (Settings are ignored.) Input use setting
Input
8
Input
7
Input
6
Input
5
Input
4
Input
3
Input
2
Input
1
D(m+1) Input signal range setting
Input 8 Input 7 Input 6 Input 5 Input 4 Input 3 Input 2 Input 1
D(m+2) Input 1: Mean value processing setting
D(m+3) Input 2: Mean value processing setting
D(m+4) Input 3: Mean value processing setting
D(m+5) Input 4: Mean value processing setting
D(m+6) Input 5: Mean value processing setting
D(m+7) Input 6: Mean value processing setting
D(m+8) Input 7: Mean value processing setting
D(m+9) Input 8: Mean value processing setting
D(m+10)
to (m+17)
Not used. (Settings are ignored.)
D(m+18)
Conversion time/resolution setting
00: Conversion time of 1 ms and resolution of 4,000
C1: Conversion time of 250 µs and resolution of 8,000
Operation mode setting
00: Normal mode
C1: Adjustment mode