194
Exchanging Data with the CPU Unit Section 5-5
CJ1W-DA021
CJ1W-DA041
I/O Word Bits
1514131211109876543210
Output
(CPU to
Unit)
n Not used. Not used. Conversion enable
--- --- Out-
put 2
Out-
put 1
n + 1 Output 1 set value
16
3
16
2
16
1
16
0
n + 2 Output 2 set value
n + 3 Not used.
n + 4 Not used.
n + 5 Not used.
n + 6 Not used.
n + 7 Not used.
n + 8 Not used.
Input
(Unit to
CPU)
n + 9 Alarm Flags Not used. Output setting error
--- --- Out-
put 2
Out-
put 1
I/O Word Bits
1514131211109876543210
Output
(CPU to
Unit)
n Not used. Not used. Conversion enable
Out-
put 4
Out-
put 3
Out-
put 2
Out-
put 1
n + 1 Output 1 set value
16
3
16
2
16
1
16
0
n + 2 Output 2 set value
n + 3 Output 3 set value
n + 4 Output 4 set value
n + 5 Not used.
n + 6 Not used.
n + 7 Not used.
n + 8 Not used.
Input
(Unit to
CPU)
n + 9 Alarm Flags Not used. Output setting error
Out-
put 4
Out-
put 3
Out-
put 2
Out-
put 1