229
Specifications Section 6-1
Range: –10 to 10 V
Note The conversion values and set values for a range of –10 to 10 V will be as fol-
lows:
0000
F830
F768
07D0
0898
0 V
–10 V
–11 V
11 V
10 V
Resolution: 4,000
Set value (16-bit binary data)
Analog output signal
16-bit binary data BCD
F768 –2200
::
FFFF –1
0000 0
0001 1
::
0898 2200