Data Memory Coding Sheets Appendix C
Note m=20000+ unit number x 100 is allocated as the DM number.
DM word
Setting contents
15 8 7
0
m
m+1
m+2
m+3
m+4
m+5
Input use
designation
03 02 01 00
Input 2
Input 1
Use Designation
0: Do not use.
1: Use
07 06 05 04 03 02 01 00
Input 2
Input 1
Signal Range Setting
00:10 to 10 V
01: 0 to 10 V
10: 1 to 5 V / 4 to 20 mA (change using voltage/current switch)
11: 0 to 5 V
15 12 11 08 07 04 03 00
16
3
16
2
16
1
16
0
Mean Value Processing Setting
0000: Mean value processing with 2 buffers.
0001: No mean value processing
0002: Mean value processing with 4 buffers.
0003: Mean value processing with 8 buffers.
0004: Mean value processing with 16 buffers.
0005: Mean value processing with 32 buffers.
0006: Mean value processing with 64 buffers.
Input signal
range setting
Input 4
Input 3
Input 4
Input 3
Input 1: Mean value processing setting
Input 2: Mean value processing setting
Input 3: Mean value processing setting
Input 4: Mean value processing setting
15 12 11 08
16
3
16
2
07 04 03 00
16
1
16
0
m+18
Conversion time/
resolution setting
Operation mode
setting
Conversion Time/Resolution Setting
00: Conversion time of 1 ms and resolution of 4,000
C1: Conversion time of 250 µs and resolution of 8,000
Operation Mode Setting
00: Normal mode
C1: Adjustment mode