383
Data Memory Coding Sheets Appendix C
Note m=20000+ unit number x 100 is allocated as the DM number.
DM word
Setting contents
15 8 7
0
m
m+1
m+2
m+3
Output 1: Output status
when conversion stopped
Output 2: Output status
when conversion stopped
01 00
Use Designation
0: Do not use.
1: Use
03 02 01 00
Signal Range Setting
00: 10 to 10 V
01: 0 to 10 V
10: 1 to 5 V / 4 to 20 mA
11: 0 to 5 V
07 04 03 00
16
1
16
0
00: CLR (0 or minimum value for each range output)
01: HOLD (Hold prior output value.)
02: MAX (Output maximum value of ran
g
e.)
Output Status when Conversion Stopped
Output signal
range setting
Output 2
Output 1
Output 2
Output 1
Output use
designation
---
---

Table of Contents