B
Brian TerrySep 9, 2025
What should I check for a Discrepancy Error at Safety Input in Omron I/O Systems?
- NnguyentroySep 10, 2025
To address a Discrepancy Error at Safety Input in Omron I/O Systems: * Ensure the input signal wire isn't contacting the positive side of the power source. * Make sure the input signal wire does not have an earth fault. * Make sure the input signal wire is not disconnected. * Make sure there is not a short circuit between input signal wires. * Make sure a failure has not occurred in the connected device. * Make sure the set value of the discrepancy time is valid. To recover from these failures, the latch input error time must have passed, the cause of the error must have been removed, and the target safety input terminal inputs must turn OFF. Reconfiguration is required when changing the discrepancy time.