5 Advanced Operations
5 - 36
E5@C Digital Temperature Controllers User’s Manual (H174)
5-13 Using the Transfer Output
A transfer output can be used on models that have a transfer output. With the E5CC-U* or E5GC, if the
control output is a linear current output, the control output can be used as a simple transfer output. For
details on a simple transfer output, refer to 5-13-2 Simple Transfer Output Function.
* The Digital Controller must be manufactured in May 2014 or later (version 2.2 or higher).
z Precision and User Calibration
* For details on calibration, refer to Section 6 Parameters.
Transfer Output Signal (Initial Setting Level)
You can use the Transfer Output Signal parameter to specify whether to output a current or voltage
from the transfer output.
Terminal Arrangement
z Transfer Output Type (Initial Setting Level)
You can use the Transfer Output Type parameter to specify any of six types of data to output.
*1 When the SP is selected, the remote SP will be output while the SP Mode parameter is set to the Remote SP
Mode.
*2 This function can be set for a Position-proportional Model, but the setting will be disabled.
*3 This function can be set for standard control or for a Position-proportional Model, but the setting will be
disabled.
*4 This parameter is displayed only for a Position-proportional Model and only when there is a potentiometer
input.
5-13-1 Transfer Output Function
Precision User calibration
±0.3% FS Supported.*
Setting range Default
4-20: 4 to 20mA
4-20
1-5v: 1-5 V
Transfer output type Display Setting range
OFF (default) off ---
Set point
*1
sp
SP lower limit to SP upper limit
Set point during SP ramp sp-m SP lower limit to SP upper limit
PV
pV
Input setting range lower limit to input setting range upper limit or
Scaling lower limit to scaling upper limit
MV monitor (heating)
*2
mV
−5.0 to 105.0 (heating/cooling control: 0.0 to 105.0)
MV monitor (cooling)
*3
c-mV
0.0 to 105.0
Valve opening
*4
V-m
−10.0 to 110.0
V
I
P
R
Q
Transfer output
V
I
Transfer output
31
33
32
E5CC
Option number: 006
E5EC/E5AC
Option number: 011, 012, 013, or 014