6 Parameters
6 - 58
E5@C Digital Temperature Controllers User’s Manual (H174)
clfl
Close/Floating A Position-proportional Model must be used.
• The Close/Floating parameter is used to set the control method for a
Position-proportional Model.
calb
Motor Calibration A Position-proportional Model must be used.
The Motor Calibration parameter is used to calibrate the valve position and automatically set
the travel time from completely open to completely closed. You can then check the valve
opening with the Valve Opening Monitor parameter.
If you set the Motor Calibration parameter to ON, the valve will open completely and close
completely, and then the setting of the parameter will change to OFF when the measure-
ment has been completed. “ERR” will be displayed if any of the following errors occurs dur-
ing execution. If an error occurs, check the wiring and other factors and execute motor
calibration again.
• The potentiometer input value does not change or changes backward between
completely open and completely closed because the wiring is wrong.
• The value of the potentiometer input is incorrect because of a broken wire, noise, or other
factor.
* Do not change to any other parameter during calibration.
z Related Parameters
Travel Time (Initial Setting Level): Page 6-59
Function
Setting
Setting range Default
flot: Floating control
clos: Close control
flot
Function
Operation
See
See