6 Parameters
6 - 62
E5@C Digital Temperature Controllers User’s Manual (H174)
init
Parameter Initialization
• This parameter returns all parameter settings to their defaults.
• After the initialization, the set value automatically turns OFF.
mspu
Number of Multi-SP Points
The Digital Controller must not have event inputs
or the Event Input Assignment 1 to Event Input
Assignment 6 parameters must not be set to
“Multi-SP No. switching bit 0” to “Multi-SP No.
switching bit 2.”
This parameter sets the number of Multi-SP points that will be used with key operations
(none or 2 to 8).
spru
SP Ramp Time Unit The ST parameter must be set to OFF.
• This parameter sets the time unit for the rate of change during SP ramp operation.
z Related Parameters
Ramp SP Monitor (Operation Level): 6-10
SP Ramp Set Value and SP Ramp Fall Value (Adjustment Level): Page 6-33
Function
Setting
Setting range Default
off: Initialization is not executed. off