6 Parameters
6 - 74
E5@C Digital Temperature Controllers User’s Manual (H174)
mani
Manual MV Initial Value
Control must be set to 2-PID control.
A Position-proportional Model set to Close Control
with the Direct Setting of Position-proportional MV
parameter set to ON must be used.
This parameter sets the initial value of the manual MV to use after control moves from Auto-
matic Mode to Manual Mode.
If the Manual MV Limit Enable parameter is set to ON, the setting range will be the MV lower
limit to the MV upper limit.
z Related Parameters
Manual Output Method (Advanced Function Setting Level): Page 6-73
Manual MV Limit Enable (Advanced Function Setting Level): Page 6-86
Function
Setting
Setting range Unit Default
Standard control: −5.0 to 105.0 % 0.0
Heating/cooling control: −105.0 to 105.0
See