6 - 83
6 Parameters
E5@C Digital Temperature Controllers User’s Manual (H174)
6-8 Advanced Function Setting Level
6
rs-t
Remote SP Input
There must be a remote SP input.
ST must be set to OFF.
This parameter sets the input type for the remote SP.
rspu
Remote SP Enable
There must be a remote SP input.
The ST parameter must be set to OFF.
This parameter is set to ON to enable setting SP Mode. You can set the SP Mode parameter
to LSP to select a local SP or to RSP to select a remote SP. If this parameter is set to OFF,
only a local SP can be used.
z Related Parameters
SP Mode (Adjustment Level): Page 6-21
000
Function
Setting
Setting range Default
4-20: 4 to 20mA
4-20
0-20: 0 to 20mA
1-5v: 1 to 5V
0-5v: 0 to 5V
0-10: 0 to 10V
000
Function
Setting
Setting range Default
on: Enabled or off: Disabled off
See