89
Using Event Inputs Section 4-5
Set points 0, 1, 2 and 3 will be set according to the ON/OFF states of event
inputs 1 and 2.
4-5-4 Operation Commands Other than Multi-SP
The following table shows the functions assigned when an Event Input
Assignment (1 or 2) is displayed.
Note (1) PRST (Program Start) can be set even when the Program Pattern param-
eter is set to OFF, but the function will be disabled.
(2) This function can be set for heating/cooling control, but the function will
be disabled.
When any of the following functions is set for an Event Input Assignment
parameter, the same function cannot be set for another Event Input Assign-
ment parameter: STOP (RUN/STOP), MANU (Auto/Manual Switch), PRST
(Program Start), DRS (Invert Direct/Reverse Operation), AT-2 (100% AT Exe-
cute/Cancel), AT-1 (40% AT Execute/Cancel), WTPT (Setting Change Enable/
Disable), or LAT (Alarm Latch Cancel). Turn event inputs ON and OFF while
the power is being supplied. Event input ON/OFF changes are detected for
inputs of 50 ms or longer. (However, inputs of 250 ms or longer is determined
using logic operations.)
The functions are described in detail below. Event inputs 1 and 2 are taken as
examples.
Number of Multi-SP Uses Setting
2. Select the Number of Multi-SP Uses parameter by pressing the M Key.
3. Use the U Key to set the parameter to 2.
ev-m
1
Number of
Multi-SP Uses
ev-m
2
E5CN
EV1
EV2
EV1
EV2
+
−
+
EV1
EV2
EV1
EV2
+
−
+
E5AN/EN
11
12
13
11
12
13
Setting Function
none None
stop RUN/STOP
manu Auto/Manual
prst Program Start (See note 1.)
drs Invert Direct/Reverse Operation
at-2 100% AT Execute/Cancel
at-1 40% AT Execute/Cancel (See note 2.)
wtpt Setting Change Enable/Disable
lat Alarm Latch Cancel