EasyManuals Logo

Omron E5CN User Manual

Omron E5CN
320 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #147 background imageLoading...
Page #147 background image
122
Using the Extraction of Square Root Parameter Section 4-17
4-16-3 MV at PV Error
The MV to be output for input errors can be set.
The MV at stop takes priority when stopped and the manual MV takes pri-
ority in manual mode.
Note The order of priority is as follows: Manual MV > MV at stop > MV at PV error.
The order of priority of the MVs is illustrated in the following diagram.
Note When the Manual MV Limit Enable parameter is set to ON, the setting range
will be the MV lower limit to the MV upper limit.
4-17 Using the Extraction of Square Root Parameter
Extraction of Square
Roots
Parameter name Setting range Unit Default
MV at PV ERROR 5.0 to 105.0 for standard
control
105.0 to 105.0 (heating/cool-
ing control)
%0.0
PID
calculations
MV upper limit
Manipulated variable
Time
MV lower limit
MV at PV Error
Input error
RUN/STOP
MV at Stop
Manual MV
(See note.)
Auto/manual switch
Output
Extraction of Square Root Enable
For analog inputs, the Extraction of Square Root parameter is provided
for inputs so that differential pressure-type flow meter signals can be
directly input.
The default setting for the Extraction of Square Root parameter is OFF.
The Extraction of Square Root Enable parameter must be set to ON in
order to use this function.
Extraction of Square Root Low-cut
Point
If the PV input (i.e., the input before extracting the square root) is higher
than 0.0% and lower than the low cut point set in the Extraction of
Square Root Low-Cut Point parameter, the results of extracting the
square root will be 0.0%. If the PV input is lower than 0.0% or higher
than 100.0%, extraction of the square root will not be executed, so the
result will be equal to the PV input. The low-cut point is set as normal-
ized data for each input, with 0.0 as the lower limit and 100.0 as the
upper limit for the input setting range.
sqr
off
sqrp
0.0

Table of Contents

Other manuals for Omron E5CN

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5CN and is the answer not in the manual?

Omron E5CN Specifications

General IconGeneral
CommunicationRS-485 (optional)
MountingPanel Mount
Control MethodON/OFF
Input TypeThermocouple, RTD
Supply Voltage100 to 240 VAC
Output TypeRelay, Voltage (for driving SSR), Current
Display Type7-segment LED
Size48 x 48 mm
Control OutputRelay, Voltage (for driving SSR), Current
Alarm Output1 or 2 outputs
Dimensions48 x 48 x 78 mm
Ambient Operating Temperature-10 to 55°C
Protection RatingIP66

Related product manuals