72
Setting the No. 3 Display Section 3-11
3-11 Setting the No. 3 Display
This section describes how to set the No. 3 Display (E5AN/EN). The Multi-SP,
MV, or soak time remain can be displayed on the No. 3 display.
3-11-1 PV/SP Display Selection
The following table shows the set values and display contents for the PV/SP
Display selection.
A 2-level display is set when shipped from the factory. (set value: 0)
A 3-level display is activated if parameters are initialized. (set value: 4)
Note For details on setting the MV for heating and cooling control, refer to MV Dis-
play for Heating and Cooling Control below.
When 1, 2, 5, or 6 is selected, press the M Key to display the next value set
for the PV/SP display (display 2).
Example: When the PV/SP Display Screen Parameter Is Set to 2
MV Display for
Heating and Cooling
Control
Select either the manipulated variable (heating) or manipulated variable (cool-
ing) as the MV to be displayed for PV/SP/MV during heating and cooling con-
trol. The MV Display Selection parameter is displayed only when heating/
cooling control is being performed and PV/SP/MV is selected in the PV/SP
Display Screen parameter or a Monitor/Setting Item Display parameter.
Set value Display contents
0 Only PV/SP is displayed (with no No. 3 display.)
1 PV/SP/Multi-SP and PV/SP/MV are displayed in order. (See note.)
2 PV/SP/MV and PV/SP/Multi-SP are displayed in order. (See note.)
3 Only PV/SP/Multi-SP is displayed.
4 Only PV/SP/MV is displayed. (See note.)
5 PV/SP/Multi-SP and PV/SP/Soak time remain are displayed in order.
6 PV/SP/MV and PV/SP/Soak time remain are displayed in order. (See
note.)
7 Only PV/SP/Soak time remain is displayed.
25
100
50.0
25
100
sp0
Press the
M key
PV/SP/MV PV/SP/Multi-SP
Operation Level
PV/SP (Display 1)
C
C
PV/SP (Display 2)
Parameter name Set value Symbol Display contents
MV Display Selection O o Manipulated variable
(heating)
C-O c-o Manipulated variable
(cooling)

Table of Contents

Other manuals for Omron E5CN

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5CN and is the answer not in the manual?

Omron E5CN Specifications

General IconGeneral
CommunicationRS-485 (optional)
MountingPanel Mount
Control MethodON/OFF
Input TypeThermocouple, RTD
Supply Voltage100 to 240 VAC
Output TypeRelay, Voltage (for driving SSR), Current
Display Type7-segment LED
Size48 x 48 mm
Control OutputRelay, Voltage (for driving SSR), Current
Alarm Output1 or 2 outputs
Dimensions48 x 48 x 78 mm
Ambient Operating Temperature-10 to 55°C
Protection RatingIP66