240
User Calibration
Section 6-2
6-2 User Calibration
The E5CN/CN-U/AN/EN is correctly calibrated before it is shipped from the
factory, and normally need not be calibrated by the user.
If, however, it must be calibrated by the user, use the parameters for calibrat-
ing temperature input and analog input. OMRON, however, cannot ensure the
results of calibration by the user. Also, calibration data is overwritten with the
latest calibration results. The default calibration settings cannot be restored
after user calibration. Perform user calibration with care.
6-2-1 Calibrating Inputs
The input type selected in the parameter is used for calibration. The input
types are as follows:
Controllers with Thermocouple/Resistance Thermometer Universal Inputs
Thermocouple: 16 types
Infrared temperature sensor: 4 types
Analog input: 1 type
Platinum resistance thermometer: 5 types
Controllers with Analog Inputs
Current input: 2 types
Voltage input: 3 types
6-2-2 Registering Calibration Data
The new calibration data for each item is temporarily registered. It can be offi-
cially registered as calibration data only when all items have been calibrated
to new values. Therefore, be sure to temporarily register all items when you
perform the calibration. When the data is registered, it is also recorded that
user calibration has been performed.
Prepare separate measuring devices and equipment for calibration. For
details on how to handle measuring devices and equipment, refer to the
respective instruction manuals.
6-3 Thermocouple Calibration (Thermocouple/Resistance
Thermometer Input)
Calibrate according to the type of thermocouple: thermocouple 1 group
(input types 5, 7, 11, 12, 15) and thermocouple 2 group (input types 6, 8,
9, 10, 13, 14, 16, 17, 18, 19, 20, 21, 22, 24, 25).
When calibrating, do not cover the bottom of the Controller. Also, do not
touch input terminals/pins (terminals 4 and 5 on the E5CN, pins 1 and 2
on the E5CN-U, and pins 19 and 20 on the E5AN/EN) or compensating
conductors.

Table of Contents

Other manuals for Omron E5CN

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5CN and is the answer not in the manual?

Omron E5CN Specifications

General IconGeneral
BrandOmron
ModelE5CN
CategoryTemperature Controller
LanguageEnglish

Related product manuals